CISA rates Danfoss AK-SM 8xxA CVE-2026-129713 9.8 up to 5.4.0; no fix date, no exploitation reported

CISA's advisory of 24 November rates an unauthenticated flaw in Danfoss AK-SM 8xxA refrigeration controllers 9.8 for versions up to 5.4.0. Danfoss promises a fix in 5.5.x without a date; CISA says no exploitation of it has been reported to it.

By · LinkedIn · · 18 min read

The record has been public 5 days, the fix has no date, and no source ties the flaw to an attack

CISA released ICS advisory ICSA-26-328-03 on Tuesday 24 November 2026 for the Danfoss AK-SM 8xxA Series controller: CVE-2026-129713, a stack based buffer overflow in an "unauthenticated CGI handler", scored 9.8 on CVSS v3, affecting versions up to and including 5.4.0. Danfoss, which is the CVE numbering authority for its own products, published the CVE record on Friday 20 November at 10:49 UTC and says the fix is in "upcoming software version 5.5.x", without a date. This site read CISA's advisory as saved from a browser tab at about 16:33 UTC on Wednesday 25 November 2026, the CVE record and the NVD record at about 16:40 UTC, and BleepingComputer's article, which carries an 11:13 time stamp at UTC minus 5, that is 16:13 UTC (derived from the offset in its page data).

The dates, derived. The record has been public 5 days at this read (20 to 25 November) and was public 4 days before CISA's advisory. Its ID was reserved on Monday 16 November, 35 days after 12 October and 14 days after 2 November, the two attack dates BleepingComputer links to Danfoss controllers. Those dates are 44 days (11 October) and 43 days (12 October) before the advisory, and 2 November is 22 days before it; the two attack dates are 21 days apart (12 October to 2 November). Every figure in this paragraph is this site's arithmetic from dates printed on the pages, with weekdays checked.

What those numbers do not establish. They do not show that any attack used this flaw. CISA's own sentence says "No known public exploitation specifically targeting these vulnerabilities" has been reported to it at this time: that is CISA's statement, in a page whose only revision is the initial publication of 24 November. BleepingComputer says a supplier said the attackers used "the same vulnerability previously seen in the October attacks in France", and prints no CVE number for any attack. The identifier was reserved only after both waves. Brief 567 on this site traced that same-vulnerability claim to one installer: see below.

Who speaks. Danfoss makes the controllers and wrote the CVE record. CISA wrote the advisory. BleepingComputer is a secondary source, used here to find primaries and for the attack paragraph. The reporter named by CISA works at Midnight Blue, a security consultancy that sells research and design services (its own homepage says so); its own post about Danfoss controllers is read below. The Danfoss advisory page named in the CVE record (DSA-2026-12-01) answered this site's one request with a 403 and was not worked around, so its own text was not read; the CVE record carries Danfoss's solution and workaround wording.

What CISA and the CVE record state, and what they leave out

This site's summary of four sources read on 25 November 2026 between 16:31 and 16:42 UTC. Grey dashed cells mark what a source does not state; amber rows mark where the sources differ.

CISA's advisory (saved at about 16:33 UTC) and Danfoss's CVE record (read at about 16:40 UTC) on 25 November 2026: what they state, and what they do not

TopicStatedNot stated
The flawCVE-2026-129713, a stack based buffer overflow in an "unauthenticated CGI handler". No authentication is needed. It can cause a web server restart and "hypothetically potential" code execution with "webserver privileges" (CISA; the record carries the same description).Which handler, how it is reached, or how the overflow behaves in practice. This brief does not look for it.
The versionsAK-SM8xxA up to and including 5.4.0 (CISA). The record gives "version 0" to 5.4.0.The first affected version. Whether 5.4.0 is the newest release. Any fixed version number beyond the label 5.5.x.
The scoresCISA: CVSS v3 9.8, with no vector and no scorer named. Danfoss's record: CVSS v4.0 base 9.3, critical, with a vector. NVD: its only score is Danfoss's v4.0 one, marked Secondary.A v3 vector, and who produced the v3 score.
Product and sectorCISA: Commercial Facilities, deployed worldwide, headquarters in Denmark. BleepingComputer: controllers for refrigeration, HVAC and lighting at food retailers; Danfoss calls the line the AK-SM 800A Series (820A, 850A, 880A).How many devices exist. CISA's page prints no count; BleepingComputer's sentence that the number is unclear is its own.
The fixThe record: fixed in "upcoming software version 5.5.x", and Danfoss will remove the option to disable Strict mode. BleepingComputer: no patch is available now.A date. What removing the option changes. Whether 5.5.x is the next release after 5.4.0.
WorkaroundsThe record lists four: no internet exposure on a public address, remote access only through a secure VPN or a protected network, the "Strict mode" setting, and strong passwords.Whether any workaround closes this flaw. The record calls them workarounds and says nothing more.
ExploitationCISA: none specifically targeting it has been reported to CISA. The KEV catalogue has no entry.Whether any attack used it. The record is silent.
The reporterCISA: a researcher at Midnight Blue reported it to CISA. The record marks its discovery as external.Anything else about how or when it was found. The researcher is not named here.

CISA's recommended practices, as the advisory prints them, are the same three items BleepingComputer repeats: minimise network exposure so control system devices are not reachable from the internet, keep control networks behind firewalls and isolated from business networks, and use a VPN where remote access is required, updated to the latest version, recognising that a VPN is only as secure as the devices it connects. CISA also asks for an impact analysis and risk assessment before any defence is deployed. The advisory prints no indicator, no request and no path. Nothing in it is an artifact a reader can hunt for, so this brief has no technical section beyond the score record below.

Two scores for one flaw: 9.8 from CISA, 9.3 from Danfoss

The two numbers are not a disagreement. They come from different versions of the scoring system. CISA prints "v3 9.8" and no vector, so the 9.8 cannot be rebuilt from the page. Danfoss's CVE record carries a CVSS v4.0 score and prints the vector, and NVD, whose status is still "Awaiting Analysis", shows that same Danfoss score as its only one, marked Secondary. Which of them a vulnerability management tool will sort by depends on the version it reads.

Text
baseScore: 9.3
baseSeverity: CRITICAL
vectorString: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
affected: AK-SM8xxA, version 0, lessThanOrEqual 5.4.0, versionType custom
cwe: CWE-121 Stack-based buffer overflow
NVD vulnStatus: Awaiting Analysis
Danfoss's CVE record for CVE-2026-129713, with NVD's status line, read on 25 November 2026 at about 16:40 UTC. Field names joined to values by this site; every value is as printed.

Reading the vector (this site's reading of the standard abbreviations, not Danfoss's words): reachable over the network, low complexity, no attack requirements, no privileges, no user interaction, high impact on confidentiality, integrity and availability of the vulnerable system, and none on other systems. It says nothing about whether the controller must be reachable from the internet in practice: "network" in a score means reachable over a network, not the open internet.

The attacks BleepingComputer links, and who has said what

Drawn by this site on a time scale of 17 pixels a day. Attack dates are as BleepingComputer gives them; every other marker is the date a saved page prints. Green spans are this site's arithmetic. The hatched span is not a forecast.

BleepingComputer's paragraph on prior incidents says that on 11 and 12 October several French supermarkets and food retailers lost heavily after attacks it describes as attributed to an Iranian unit, and that Danfoss and Copeland or Dixell controllers were compromised and their defrost settings altered. It says that on 2 November at least 115 stores in seven countries had equipment shut down or settings changed, that a supplier said the same vulnerability was used again, and that on the same day attackers suspected of the same campaign altered cold storage settings at three facilities of a refrigeration supplier for the French national blood service. It links its own earlier articles for each, not the primaries. This site read three of them or their primaries.

What the sources say about the attacks, and where they differ (BleepingComputer 25 November, its 2 and 9 November articles, CERT-FR's page of 9 November, and this site's briefs 304 and 567)

PointWhat the sources sayDifference or gap
Same flaw as OctoberBleepingComputer: a supplier said the attackers used the same vulnerability as in October, indicating Danfoss systems were involved again. Brief 567 (2 November) traced the claim to Belga and one installer's executive: four reports, one origin.No CVE is named for either wave. "Indicating that Danfoss systems were involved again" is BleepingComputer's inference; brief 567 also records a report of Copeland equipment in Belgium.
Who did itFrance's coordination centre for cyber crises (C4: ANSSI, the military cyber command, DGA, DGSE and DGSI) says the Iranian IRGC sponsored the 11 and 12 October refrigeration attack and that the unit Shahid Kaveh carried it out, on what the report calls a bundle of clues: infrastructure shared with reconnaissance of other industrial equipment, a device search tool the group is said to use, a relay on a propaganda outlet tied to the unit on 13 October, and traces of Farsi in the attack infrastructure (CERT-FR report CTI-009, 9 November, read in full and translated by this site). BleepingComputer 25 November names the same unit.This is France's attribution and an allegation here; this brief does not assess the evidence. BleepingComputer 9 November says France attributed only the October attacks, not the later ones, and the report does not mention the second wave. The report names no vendor, no product, no CVE and no way in. It gives about 700 sites and at least 15 fires for October.
Earlier briefsBrief 304 (12 October): no source read gave a claim of responsibility, group, motive or nationality. Brief 567 (2 November, with its 4 November note): no claim of responsibility, and The Record said it was unclear whether the same people were behind both waves.Both briefs predate France's 9 November attribution. Neither mentions any CVE for the Danfoss 8xxA flaw, which did not exist yet.
Which Danfoss productsBleepingComputer: AK-SM and AK-SC controllers were compromised in October. Brief 304: Danfoss told franceinfo that most hit units were end of life AK-SM800 and AK-SC355 systems.CISA's flaw is in the AK-SM 8xxA series. No page says whether any unit hit in October or November was an 8xxA, or on which version.
Countries and storesBleepingComputer 25 November: at least 115 stores in 7 countries listed, Romania among them (the count of seven is this site's, derived from the list). BleepingComputer 2 November: more than 115 stores in 6 countries, without Romania. Brief 567's 4 November note: at least 11 countries (The Record).The same figure of 115 with a different country list. Romania appears in none of the other pages read. This brief does not choose a count.
The blood serviceBleepingComputer: "on the same day" (2 November), a supplier to the service, three facilities. Brief 567's note, relaying the service's statement of 3 November through The Record: three sites, reached through a third party refrigeration provider.The tampering date is not given in what was read. No source read says which controller or flaw.
Drawn by this site from the sources read on 25 November 2026. Arrows join cards that are compared, not a data flow. The blocked arrow marks a link that no page draws.

The honest summary is a gap, not a link. CISA reports no exploitation of this flaw to it. Danfoss's record is silent on attacks. France's report, dated seven days before the identifier was reserved (derived), names no CVE, no vendor and no way in. Midnight Blue's post does not name this CVE. BleepingComputer's "the same" is a supplier's statement, and the October units Danfoss described earlier were mainly not the 8xxA series. All of that is compatible with this flaw having been used, and with it not having been. The pages do not decide it. For what the earlier waves did and did not establish when they broke, see this site's briefs on the French attack and on the second wave.

Midnight Blue says six; CISA lists one

Midnight Blue published its own post, about the AK-SM800A. The page prints "November, 2026"; the firm's blog list labels it "Oct 2026"; the post's text refers to the 2 November wave in the past, and the site's source says it was last published at 14:15 UTC on 18 November. So the post was on the site by 18 November (inference), two days before the CVE record went public (derived), and this brief reports both dates without choosing one. Midnight Blue sells security consultancy services, as its own homepage says.

The post says its researcher found "6 pre-authentication remote code execution 0-day vulnerabilities" in the latest firmware when written, 5.3.2, with "CVEs: Pending". Its overview lists the affected versions as all up to and including 5.3.2 and the type as multiple (6) stack based buffer overflows. It says a coordinated disclosure process with Danfoss was under way and withholds the technical detail. It says the tested application runs as root. It describes a session control scheme with three levels whose strictest, "strict", has been the default since 4.0, and says at least one trivial memory corruption flaw exists in that scheme before login. It recommends against spending scarce resources on patching and for removing internet exposure. It also says, relaying SentinelOne, that "attribution remains open" for the October and November incidents and that analysts should not assume one actor. This brief prints none of the post's technical detail.

Midnight Blue's post against CISA's advisory and the CVE record, all read on 25 November 2026

PointMidnight Blue postCISA and the CVE record
How many flawsSix, in the tested firmwareOne, CVE-2026-129713
VersionsAll up to and including 5.3.2, the latest when writtenUp to and including 5.4.0
PrivilegesSays the tested application runs as root"webserver privileges"
CVE identifiersPending; the post does not name CVE-2026-129713One identifier; the record names a reporter only as external
Is this CVE one of the sixNot statedNot stated. CISA credits a researcher at the same firm for this CVE

The match in firm, bug class and version numbers makes it tempting to say CVE-2026-129713 is one of the six. No page says so, and the differences in count, version and privileges are real. This brief treats it as likely only in the sense that it is unproven (inference), and treats the privilege difference as open: CISA and the record describe "webserver privileges", the post says root for its tested application.

Strict mode: the label the fix leans on, and what no page explains

Danfoss's record does two things with the term. Its workaround list tells owners to configure the units to "Strict mode", which it says ensures higher security levels. Its solution says that "we will remove the option that customers can disable the product Strict mode". BleepingComputer repeats the second sentence. CISA's page does not mention it at all.

What the setting is comes from other sources. Midnight Blue describes it as the strictest of three session control levels, the default since version 4.0, which enforces encrypted connections and session tokens. Brief 304 recorded, from a Danfoss product page read on 12 October, a strict session mode that requires encrypted sessions from software package 4.0. Whether that is the same setting Danfoss means in this record is not stated on any page read today.

Strict mode, as the pages read on 25 November 2026 treat it

QuestionWhat a page saysNot stated
What it isDanfoss's record: it ensures higher security levels. Midnight Blue: the strictest session control level, default since 4.0.Danfoss's own definition in the record. Whether the two descriptions are the same setting.
Does it stop this flawNothing in the record says it does. Midnight Blue says at least one other flaw is reachable with strict session control on.Whether CVE-2026-129713 is reachable with it on. Midnight Blue does not say which flaw it means.
What removing the off switch changesDanfoss will remove the option to disable it, in the fix.What happens to units upgraded from older versions. What 5.4.0 and earlier units can do now.

One inference, labelled: a vendor that lists a setting as a workaround and then promises to remove its off switch is signalling that the setting matters for exposure. That is a reading of intent. It does not show that the flaw is unreachable with the setting on, and it does not tell an owner what to change. This brief gives no setting changes beyond what CISA prints.

Where the sources differ in wording, and how this brief handles each

Differences between CISA, Danfoss's record, Midnight Blue and BleepingComputer on 25 November 2026

PointThe sourcesHandling
"Potentially" or "hypothetically potential"CISA and the record: "hypothetically potential" code execution. BleepingComputer: "potentially" achieve it.The CNA wording is the primary; BleepingComputer paraphrased it. Not a difference of fact.
Web server or rootCISA and the record: "webserver privileges". Midnight Blue: the tested application "runs as root".Kept as a difference. The pages do not say whether they describe the same flaw.
VersionsCISA and the record: up to and including 5.4.0. Midnight Blue: up to and including 5.3.2, the latest when written.Different ranges. The record gives no reason; no version arithmetic is computed here.
One flaw or sixCISA lists one CVE. Midnight Blue says six, pending.Both reported; no link asserted.
ScoresCISA v3 9.8, no vector. The record v4.0 9.3 with a vector.Different scoring versions; each attributed.
Number of devicesCISA prints "worldwide" and no count. BleepingComputer says the number is unclear and attributes the note to CISA.The count is not stated by any primary read. This brief prints no scan service figure.
Dates of the postMidnight Blue: "November, 2026" on the page, "Oct 2026" in its blog list.Both printed; the site's last publish time is a limit, not a date.

What to do, in order

CISA's guidance comes first, as the advisory prints it. The suggestions after it are this site's, written for the people who own the stores, the installers and the networks; they are not a reading of any law or contract, and none of them asks anyone to change a controller setting.

Take this with you

CISA's guidance, then this site's suggestions

  • CISA: minimise network exposure for all control system devices so they are not accessible from the internet.
  • CISA: locate control system networks and remote devices behind firewalls and isolate them from business networks.
  • CISA: when remote access is required, use more secure methods such as VPNs, keep the VPN updated, and remember it is only as secure as the connected devices.
  • CISA: perform impact analysis and risk assessment before deploying defensive measures.
  • CISA: report suspected malicious activity through your established internal procedures and to CISA.
  • This site's suggestion: list every AK-SM 8xxA controller and its software version, and ask your supplier or installer for the list if you do not hold it.
  • This site's suggestion: confirm in writing, per site, that the controller's web interface is not reachable from the internet. Ask your network team to check from inside your own network and equipment. Do not scan from outside.
  • This site's suggestion: ask your installer in writing which of the workarounds in Danfoss's record apply to each unit, and have them run CISA's impact analysis first.
  • This site's suggestion: record who receives Danfoss's notice of the 5.5.x release and who decides to install it, because no page read prints a date.
  • This site's suggestion: agree in advance what the store does if cold chain monitoring shows a temperature alert at 03:00: who checks by hand and who is called. This is a food safety step, not a control change.
  • This site's suggestion: keep dated copies of the CISA advisory, the CVE record and Danfoss's advisory. They will change.

The question the record leaves open

CISA says no exploitation has been reported to it. Danfoss says a fix is coming and prints no date. A security firm says there may be more. None of that tells a retailer what is in its stores. If the controller that logs your cold chain has an unauthenticated flaw and the fix has no date, who in your organisation owns the gap until it ships?

Key facts

Sources

  1. PrimaryICS advisory ICSA-26-328-03, Danfoss AK-SM 8xxA Series, released 24 November 2026 (revision 1): CVE-2026-129713, versions up to and including 5.4.0, CVSS v3 9.8, recommended practices, no known exploitation reported to CISA. A living page, saved from a browser tab at about 16:33 UTC on 25 November 2026Cybersecurity and Infrastructure Security Agency (CISA)accessed 2026-11-25
  2. PrimaryCVE-2026-129713 record: reserved 16 November, published 20 November 2026 at 10:49 UTC, description, CWE-121, CVSS v4.0 base 9.3 with vector, workarounds, solution (5.5.x, Strict mode off option removed), reference to Danfoss advisory DSA-2026-12-01 (page not read). Read at about 16:40 UTC on 25 November 2026CVE Program (record assigned by Danfoss as CNA)accessed 2026-11-25
  3. PrimaryNVD record for CVE-2026-129713: status Awaiting Analysis, published 20 November, last modified 24 November 2026, the Danfoss v4.0 score as its only metric. Read at about 16:40 UTC on 25 November 2026NIST National Vulnerability Databaseaccessed 2026-11-25
  4. PrimaryKnown Exploited Vulnerabilities catalogue, version 2026.11.25, released 14:22 UTC, 1,796 entries: no entry for this CVE or for Danfoss (extract saved; read at about 16:41 UTC on 25 November 2026)CISAaccessed 2026-11-25
  5. PrimaryThe firm's own post on Danfoss AK-SM800A: six pre-authentication flaws claimed in firmware up to 5.3.2, CVEs pending, coordinated disclosure under way, strict session control passage, mitigation advice. Read in full at about 16:41 UTC on 25 November 2026; the exploitation passages are not stored or used. The firm sells security consultancy servicesMidnight Blueaccessed 2026-11-25
  6. PrimaryCERTFR-2026-CTI-009, 9 November 2026 (single version), landing page read at about 16:42 UTC and the report itself (PDF, French, read in full at about 16:53 UTC on 25 November 2026): France's C4 attributes the 11 and 12 October refrigeration controller attack to an IRGC sponsored unit; no CVE, vendor or entry route namedCERT-FR (ANSSI)accessed 2026-11-25
  7. Reported byCISA warns of critical unpatched flaw in Danfoss refrigeration controllers, 25 November 2026 (11:13 UTC minus 5 in its page data): the Danfoss advisory of 20 November, no patch, the paragraph on earlier attacks. Saved at about 16:31 UTC; used to find primaries and for the attack paragraph onlyBleepingComputeraccessed 2026-11-25
  8. Reported byFrance blames Iranian hackers for supermarket attacks that sparked fires, 9 November 2026: relays France's attribution and says only the October attacks were attributed. Saved at about 16:42 UTC; secondaryBleepingComputeraccessed 2026-11-25
  9. Reported byHackers disrupt refrigeration systems at European supermarkets, 2 November 2026: more than 115 stores in six countries (Romania not listed). Text saved by this site on 2 November for another brief; secondaryBleepingComputeraccessed 2026-11-25